Arima Technical Call Us +91 - 94999 74406

Kirloskar 125KVA - Arima Technical

Kirloskar 125KVA

Prime rating at rated rpm (as per ISO8528) kVA 160
Kw 100
Genset Model   KG1-125WS
Frequency HZ 50
Power factor Lagging 0.8
Voltage V 415(3Ø )
Governing class (As per ISO 8528 part-V)   G3
Noise level dBA <75
Fuel Consumption* At 100%  load Ltrs/Hr 27.4
At 75% load 20.2
At 50% load 15.3
Fuel tank capacity Ltrs 230
Overall dimensions of genset (LxWxH)^ mm 3200x1300x1795
Dry Weight of genset with canopy (approx..)^ kg 2090
Wet weight of genset with canopy(approx…)^ kg 2290
Height including Silencer kg 2400
Electrical Battery starting voltage Volts-DC 12

ENGINE

Engine Model   4K1080TA G2
Rated output(prime Continuous rating as per ISO 8528-1) Kw 114.7
Hp 156
NO. of cylinder Number 4
Cubic capacity 2 Ltrs 4.32
Bore x stroke Mm 105×125
Rated speed RPM 1500
Aspiration NA/TC/TA TA
Lube Oil change period Hrs 500
Lube oil sump capacity Max Ltrs 14
Coolant capacity Ltrs 21

ALTERNATOR

Insulation Class   Class H
Ingression protections   IP 23
Altemator Efficiency (at 100% load) 0.8pf**   92.5
Altemator Efficiency (at 75% load) 0.8pf**   93.3
Permissiable Voltage Dip at full load 0.8 pf lag   ≤20%
Time to build up rated voltage at rated RPM   < 5 sec provided engine reach the rated speed
Short circuit Ratio   0.518
Short circuit with stand time Sec <3 sec
Overload with stand capacity % 10% overload for one hours once in 12 hours