Arima Technical Call Us +91 - 94999 74406

Kirloskar 180KVA - Arima Technical

Kirloskar 180KVA

Prime rating at rated rpm (as per ISO8528) kVA 180
Kw 144
Genset Model   KG1-180WS
Frequency HZ 50
Power factor Lagging 0.8
Voltage V 415(3Ø )
Governing class (As per ISO 8528 part-V)   G3
Noise level dBA <75
Fuel Consumption* At 100%  load Ltrs/Hr 41.3
At 75% load 30.9
At 50% load 22.7
Fuel tank capacity Ltrs 460
Overall dimensions of genset (LxWxH)^ mm 4340x1740x1970
Dry Weight of genset with canopy (approx..)^ kg 3900
Wet weight of genset with canopy(approx…)^ kg 4300
Height including Silencer kg 2609
Electrical Battery starting voltage Volts-DC 24

ENGINE

Engine Model   6SL1500TA G2
Rated output(prime Continuous rating as per ISO 8528-1) Kw 183
Hp 248
NO. of cylinder Number 6
Cubic capacity 2 Ltrs 8.86
Bore x stroke Mm 118×135
Rated speed RPM 1500
Aspiration NA/TC/TA TA
Lube Oil change period Hrs 500
Lube oil sump capacity Max Ltrs 27
Coolant capacity Ltrs 32

ALTERNATOR

Insulation Class   Class H
Ingression protections   IP 23
Altemator Efficiency (at 100% load) 0.8pf** % 93
Altemator Efficiency (at 75% load) 0.8pf** % 93.6
Permissiable Voltage Dip at full load 0.8 pf lag Sec ≤20%
Time to build up rated voltage at rated RPM   < 5 sec provided engine reach the rated speed
Short circuit Ratio   0.53
Short circuit with stand time Sec <3 sec
Overload with stand capacity % 10% overload for one hours once in 12 hours