Arima Technical Call Us +91 - 94999 74406

Kirloskar 160KVA - Arima Technical

Kirloskar 160KVA

Prime rating at rated rpm (as per ISO8528) kVA 160
Kw 128
Genset Model   KG1-160WS
Frequency HZ 50
Power factor Lagging 0.8
Voltage V 415(3Ø )
Governing class (As per ISO 8528 part-V)   G3
Noise level dBA <75
Fuel Consumption* At 100%  load Ltrs/Hr 36.6
At 75% load 27.7
At 50% load 19.1
Fuel tank capacity Ltrs 300
Overall dimensions of genset (LxWxH)^ mm 4040x1540x1916
Height including Silencer kg 2385
Electrical Battery starting voltage Volts-DC 12
ENGINE    
Engine Model 6R1080TA G2  

Rated output(prime Continuous rating as per ISO 8528-1)

Rated output(prime Continuous rating as per ISO 8528-1) Kw 147
  Hp 200
NO. of cylinder Number 6
Ltrs 6.48
Bore x stroke Mm 105×125
Rated speed RPM 1500
Aspiration NA/TC/TA TA
Lube Oil change period Hrs 500
Lube oil sump capacity Max Ltrs 18
Coolant capacity Ltrs 28
ALTERNATOR    
Insulation Class   Class H

Ingression protections

Ingression protections IP 23
Altemator Efficiency (at 100% load) 0.8pf**   93
Altemator Efficiency (at 75% load) 0.8pf**   93.3
Permissiable Voltage Dip at full load 0.8 pf lag   ≤20%
Time to build up rated voltage at rated RPM   < 5 sec provided engine reach the rated speed
Short circuit Ratio   0.518
Short circuit with stand time Sec <3 sec
Overload with stand capacity % 10% overload for one hours once in 12 hours